Ratings |
---|
Item | Model |
---|
E5L-A_ | E5L-C_ |
---|
Indication accuracy | − | ±(1°C + 1 digit) max. |
Setting accuracy | − | ±(1°C + 1 digit) max. |
Hysteresis | −30 to 20°C models: Approx. 0.5 to 2.5°C (variable) 0 to 50°C models: Approx. 0.5 to 4°C (variable) 0 to 100°C models: Approx. 0.5 to 4°C (variable) 100 to 200°C models: Approx. 0.7 to 4°C (variable) | 1 to 9°C (in increments of 1°C) |
Repeat accuracy | 1% FS max | − |
Minimum scale (standard scale) | −30 to 20°C models and 0 to 50°C models: 5°C 0 to 100°C models and 100 to 200°C models: 10°C | − |
Influence of temperature | − | ±([1% of PV or 2°C, whichever is greater]+ 1 digit) max. |
Influence of voltage | − |
Sampling period | − | 2 s |
Insulation resistance | 100 M Ω max. (at 500 VDC) |
Dielectric strength | 2,300 VAC, 50/60 Hz for 1 min (between charged terminals and uncharged metallic parts, between power supply terminals and input terminals, between power supply terminals and output terminals, and between input terminals and output terminals) |
Vibration (malfunction) | Frequency of 10 to 55 Hz, 0.5-mm double amplitude for 10 min each in X, Y, and Z directions |
Vibration (destruction) | Frequency of 10 to 55 Hz, 0.75-mm double amplitude for 2 h each in X, Y, and Z directions |
Shock (malfunction) | 147 m/s 2 , 3 times each in 6 directions | 100 m/s 2 , 3 times each in 6 directions |
Shock (destruction) | 294 m/s 2 , 3 times each in 6 directions |
Electrical life expectancy (control output relay) | 100,000 operations min (at maximum applicable load) |
Memory protection | − | Non-volatile memory (100,000 write operations) |
Weight (Thermostat) | Approx. 80 g (Thermostat only) |
Degree of protection | Front panel: IP40, Terminals: IP00 |
Approved standards | − |
Conformed standards | EN 61010-1 (IEC 61010-1), Pollution Degree 2, Overvoltage Category II |
EMC Directives | EMI: EN61326-1 Radiated EMI: EN55011 Group 1 Class A Conducted EMI: EN55011 Group 1 Class A EMS: EN61326-1 Electrostatic discharge immunity: EN61000-4-2 Electromagnetic field strength immunity: EN61000-4-3 Burst noise immunity: EN61000-4-4 Conducted disturbance immunity: EN61000-4-6 Surge immunity: EN61000-4-5 Voltage dip and power interruption immunity: EN61000-4-11 |